Kompetentum Ventilations Service bedriver service samt support i hela Sverige och vi har idag tusentals återkommande kunder inom ventilation, mindre fastgheter. Under de år vi följt marknaden inom ventilation mot mindre fastgheter har vi många gånger sett oseriösa företag som offerterar samt utför arbeten med dåligt resultat. Man tar inget ansvar gentemot kunden vad gäller service eller löpande support utan har i många fall bara varit ute efter snabba jobb utan långsiktig relation till kund
måndag 2 februari 2015
If the discharge pressure exceeds
corresponding signal from the ambient thermostat to
satisfy the cooling demand.
6) When the unit stops at the end of an operating cycle, or
through a power failure, the logic module will not allow it
to start up again until 5 minutes have elapsed. This is to
protect the compressor by allowing the operating voltages
to even up.
7) If the discharge pressure exceeds 28 kg/cm2
, or the
discharge temperature is over 130°C, the logic module
will switch off the unit, leaving the system in lockout.
8) To re-set after a lock-out, turn off the power supply to the
unit. The system will re-set and the unit will start up after
5 minutes.
Winter cycle:
Thermostat in HEAT position
1) The 4-way valve is deactivated, allowing the position
for the heating circuit, which means that the indoor coil
acts as condenser and the outdoor one as evaporator.
2) If the fan operating mode in the ambient thermostat is
in the FAN ON position, the contactor is activated and
the fan functions continuously.
3) With the logic module timing, the unit will start up after
5 minutes.
4) When the first stage of the thermostat connects, the
contactor is activated and the compressor starts up. If the
operating mode of the fan is "normal", the contactor
is activated through the thermostat's heating circuit
and the fan starts up.
5) The unit will function intermittently in response to the
appropriate signals from the ambient thermostat to satisfy
the demand for heating.
6) If the unit stops, after an operating cycle, or through a
power failure, the logic module will not allow it to start up
again until 5 minutes have elapsed. This is to protect
the compressor by allowing the operating voltages to
even up.
7) If the discharge pressure exceeds 28 kg/cm2
, or the
discharge pressure is over 130°C, the logic module will
stop the unit, leaving the system in lockout.
8) To re-set after a lock-out, switch off the power to the
unit. The system will re-set and the unit start up after
5 minutes.
9) The auxiliary heater is activated when the auxiliary
heating stage of the thermostat is connected. The
logic module allows the indoor auxiliary heater to function
if the outdoor temperature is below the balance
point. If the outdoor temperature is above that set
as the balance point, the indoor heater does not function.
10) The emergency heater (complementary) is connected
when the outdoor temperature is lower than that
preselected as the operating limit (-15°C, logic module),
and the ambient thermostat demands the second heating
stage.